We recently completed an attic HVAC repair and diagnostic project for a homeowner in Las Vegas. This system used a Lennox gas furnace paired with dual outdoor condenser units. The goal was to improve cooling performance, inspect for airflow and electrical issues, and test refrigerant pressures.
Step 1: Attic Inspection of the Furnace and Ductwork
Our technicians accessed the attic to inspect the central air handler, which included a Lennox gas furnace connected to a metal plenum box. The metal ducts were sealed with mastic and mesh tape to prevent air leakage. We confirmed that all supply and return connections were intact and insulated using foil-wrapped flex duct to maintain efficiency.
We noticed prior mastic sealing around the plenum and duct seams, indicating efforts to control air leaks. The metal duct supports were still solid, and the entire unit was properly suspended from the rafters using threaded rod hangers.
Step 2: Inside the Furnace – Wiring and Burner Check
With the furnace panel opened, we checked the control board, high-limit switch, gas valve, and draft inducer motor. These are core components of any heating and cooling system.
- Draft inducer motor: Ensures safe removal of combustion gases.
- Limit switch: Protects the furnace from overheating.
- Control board: The “brain” of the furnace, managing operations.
The wiring was tidy, with all electrical connections securely mounted. We also examined the PVC condensate drain line, which was flowing properly and included a cleanout for maintenance. The yellow corrugated gas line was tightly connected with a shutoff valve and a drip leg in place.
Step 3: Refrigerant Pressure Testing – Outdoor Units
Outside, we inspected the dual condenser units. Each unit was evaluated with Yellow Jacket manifold gauges to read refrigerant pressures. This helps determine whether the system has the correct amount of R-410A refrigerant or if there’s a leak or restriction.
Here’s what we measured:
- High-side (red gauge): ~370 psi
- Low-side (blue gauge): ~110 psi
These pressure levels are within range for a properly functioning R-410A system during cooling operation in Las Vegas’s high outdoor temperatures. If pressures were too low, we would suspect a refrigerant leak or poor airflow. If too high, it might mean dirty coils or overcharging.
Step 4: Final Duct Sealing & Performance Verification
After confirming refrigerant levels and electrical operation, we resealed duct joints using additional mastic. Mastic is a thick, sticky paste used to seal air ducts. It’s applied with a brush and reinforced with mesh to stop air from leaking where ducts join together.
The return and supply plenums were reinforced to ensure maximum airflow delivery throughout the house. This greatly improves cooling performance and helps reduce utility bills.
Benefits of This HVAC Repair
- Improved central AC airflow throughout the home.
- Correct refrigerant pressure levels ensure proper cooling and energy efficiency.
- Sealed ducts reduce energy waste and keep more cool air inside the home.
- Safe gas line and furnace operation after thorough inspection.
For more details on air conditioning repair in Las Vegas, check out our AC repair services or learn about our attic HVAC installation projects.