At Fast Affordable Air, we recently serviced a commercial rooftop package HVAC unit in Las Vegas. This unit, mounted on a sloped shingle roof, was experiencing cooling performance issues that required an in-depth diagnostic and electrical inspection. Here’s a closer look at how we handled the repair and what we found using our tools and expertise.
Initial System Inspection
The customer reported that the air conditioner was not cooling the building properly, especially during peak afternoon hours. Upon accessing the rooftop unit, we conducted a thorough visual and mechanical inspection. The equipment was a packaged rooftop system charged with R-410A refrigerant, designed for both heating and cooling operations.
Refrigerant Pressure Readings
Using our Yellow Jacket digital manifold gauges, we measured the refrigerant pressures. Initial readings showed:
- High side pressure: 248.0 psi
- Low side pressure: 247.6 psi
These values were nearly identical, suggesting the system may have been off or just equalized. After running the system for several minutes, updated pressure readings showed:
- High side: 239.2 psi
- Low side: 237.9 psi
This still indicated minimal differential pressure between the suction and discharge lines, which is not typical during normal operation. It often points to a faulty compressor, a failed reversing valve (in heat pump models), or potential non-condensables in the system.
Electrical Test with Digital Multimeter
To further isolate the issue, we used a UEI G2 Phoenix DL369 clamp meter to check voltage and current readings. The digital screen displayed:
- Voltage: 18.62V
- Current: 0.136A
These low readings suggest the compressor is not drawing proper current, likely indicating it’s not running or attempting to start. A healthy compressor typically draws several amps during operation, depending on the unit size and load.
What This Means for Cooling Performance
When an air conditioner fails to create a pressure difference between the high and low sides of the system, it cannot circulate refrigerant effectively. That means no heat is being absorbed inside the building and rejected outside, which leads to poor or no cooling.
In this case, possible issues included:
- A failed or seized compressor
- Contactor or capacitor failure preventing compressor start-up
- Electrical or control board malfunctions
- Refrigerant contamination (moisture or non-condensables)
Next Steps
We recommended further testing of the compressor windings using a megohmmeter and verifying capacitor ratings to determine if components needed replacement. In many cases, replacing a dual-run capacitor or contactor can restore compressor function if caught early. Otherwise, the compressor or even the entire condenser may require replacement, depending on the severity.
By using professional tools and methodical diagnostics, we ensured our client had a clear understanding of their HVAC system’s condition. All work followed Clark County HVAC code and was performed by licensed techs at Fast Affordable Air.
To learn more about our HVAC diagnostic services or rooftop AC repairs in Las Vegas, Henderson, or North Las Vegas, visit our services page.